Wuxi Lonheo International Trade Co., Ltd. >> 18~30kv -Copper XLPE/PVC Sheathed Steel Wire Armoured Power Cable

18~30kv -Copper XLPE/PVC Sheathed Steel Wire Armoured Power Cable

18~30kv -Copper XLPE/PVC Sheathed Steel Wire Armoured Power Cable
Price: US $ 20-50/Meter
Trade Terms: FOB,CFR,CIF
Min Order: 100/Meter
Pay Type: L/C,T/T,D/P,Paypal,Money Gram

1,APPLICATION
YJV32-Copper Conductor XLPE Insulated Steel Wire Armoured PVC Sheathed Power Cable
This product is suitable for using in power distribution networks or fixed installations for industrial equipments with rated voltage up to and including 26/35KV
 
2,BASIC INFORMATION
Code Name 
YJV32
Rated Voltage (Uo/U)
18/20KV,18/30KV
Cable Structure
Copper Conductor/XLPE Insulation/Steel Wire Armoured/PVC Sheath
 
 
3,CONSTRUCTION
Conductor
Number of conductors:1,3
The conductors shall comply with the requirement given in IEC
Insulation
XLPE(Cross-linked Polyethylene) according to IEC
Sheath
PVC(Polyaluminium Chloride) according to IEC
Metal screen
Copper Tape Screen
Armoured Layer
Steel Wire
 
 
4,CABLE  STANDARDS
GB/T12706-2008,IEC,BS,ASTM and etc. upon request.
The electrical and dimensional properties of this product are measured by the Technical and Quality Assurance department at the JiangNan Cables laboratory. Cable performance in respect of conductor resistance, construction quality (workmanship), dimensional consistency, and other parameters are verified to published standards and approved product drawings. Conformance to RoHS (Restriction of the use of Hazardous Substances) is determined and confirmed.
 
 
5,CHARACTERISTICS
Conductor temperature
Maximum conductor temperature in normal use: 90ºC
Max.short-circuit temperature
Maximum shall not exceed 250ºC(5s Max,Duration)
Installation temperature
Ambient temperature under installation shall not be below 0ºC
Minimum bending radius
The bending radius of cable: (D-Diameter of cable) 
For Three Core Cable-------------------------------------≥15D
For Single Core Cable-------------------------------------≥20D

6,Voltage designation
The rated voltage of the cable for a given application shall be suitable for the operating conditions in the system in which the cable is used,and is expressed in the form of Uo/ U(Um)kV.
Where:
Uo-The rated power-frequency voltage between conductor and screen or   metallic-sheath,for which the cable designed;
U-The rated power-frequency voltage between conductors, for which the cable designed:
Urn-The maximum value of the "hight system voltage " for which the equipment may he operated.
 
7,Rated voltaged of cable applied in three phrase system are given in table
UUmUo
First classSecond class
11.20.60.6
33.61.83.6
67.23.66
101268.7
1517.58.712
20241218
35422126
Note:The first class cable suitable for one single-phrase earth-fault time does not exceed 1 min each time and Max. time not exceed 8 hours.and not exceed 125 hours in all in one year.
The second class cable suitable fir more earth-fault time and more better insulation performance.
 
8,Production Range of cable
TypeNo. of coresNominal Cross sectional area m2
Copper conductor
YJV32
 
125-630
325-630
*The armoured single-core cables are used for D.C system only. As for A.C system non-magnetic armoured material should be used. Or magnetic isolation measures should be applied.


 
9,DIMENSIONS-YJV32-18/20KV 18/30KV
Nominal cross sectional area of conductor(mm²)Nominal insulation thickness(mm)18/20KV 18/30KV YJV32
Approx overall diameter(mm)Cable weight max(kg/kn)
1×508.038.82910
1×708.040.73240
1×958.042.33610
1×1208.043.94370
1×1508.046.74810
1×1858.048.55270
1×2408.050.76040
1×3008.053.56810
1×4008.056.78050
1×5008.060.39280
1x6308.064.310830
3×508.079.79790
3×708.083.310900
3×958.087.4512220
3×1208.090.813440
3×1508.094.614880
3×1858.098.216420
3×2408.0103.718770
3×3008.0108.921250
3×4008.0116.125260
3x5008.0123.229260
3x6308.0131.334170
*Compacted conductor
 
10,Product Data Of Cable
Nominal cross-sectional area of conductor(mm²)Max.D.C resistance of conductor at 20ºC(Ω/km)Max.short circuit current of conductor at 90ºC
Copper conductorCopper conductor
250.7273.69
350.5245.15
500.3877.31
700.26810.2
950.19313.8
1200.15317.4
1500.12421.7
1850.099126.7
2400.075434.6
3000.060143.1
4000.047057.4
5000.036671.7
6300.028388.8

11,Voltage test and partial discharge test
No.Test itemsRated Voltage KV
18/20 18/30
1Power frency A.C.Voltage test (KV/5min)63
2Power frency A.C.Voltage test for 4 hours (KV)72
3Impluse voltage test(KV)170
4Partial discharge test maximum discharge at 1.73Uo pc5
The power-frequency voltage test of cables for rated voltage 21/35KV shall be done upon request according to 2.5Uo×30min or 3.5Uo×50min.

12,Capacitance of cable(reference value)
Nominal cross-sectional area of conductor(mm²)Rated Voltage KV
18/20 18/30
Capacitance/phase μF/km
250.1163
350.1251
500.1363
700.1508
950.1643
1200.1760
1500.1893
1850.2026
2400.2207
3000.2387
4000.2684
5000.2876
6300.3151


13,Inductance of cable
Nominal cross-sectional area of conductor(mm²)Rated Voltage KV
18/20 18/30
Capacitance/phase μF/km
1x500.6501
1x700.6252
1x950.6043
1x1200.5891
1x1500.5740
1x1850.5640
1x2400.5487
1x3000.5376
1x4000.5219
1x5000.5218
1x6300.5012
3x500.4396
3x700.4145
3x950.3956
3x1200.3799
3x1500.3642
3x1850.3485
3x2400.3360
3x3000.3266
3x4000.3014


14,Short circuit current of mechanic-screen
Nominal cross-sectional area of conductor(mm²)Rated Voltage KV
18/20 18/30
Short circuit current
1x501284
1x701281
1x951280
1x1201279
1x1501278
1x1851275
1x2401274
1x3001271
1x4001270
1x5001266
1x6301265
3x503031
3x703031
3x953031
3x1203031
3x1503031
3x1853031
3x2403031
3x3003031
 
 
15,Current carrying capacity of cable
Copper conductor XLPE insulated power cable for rated voltage 18/30~26/35KV
Copper ConductorNominal Cross sectional area of conductor mm2In the airIn the ground
Air temperature:40ºCAir temperature:25ºC
Single CoreThree CoreSingle CoreThree Core

 


 

50220245185215225200
70270305230265275250
95330370280315330300
120375425310360375330
150425485260400420380
185485555400455475425
240560650470525555490
300650745540595630555
400760870610680720625
5008751000-775825-
63010001160-875940-

16,Installation and Operation Condition of Cable
Max.Operation temperature of conductor-----------------------------------90ºC
Ambient air temperature--------------------------------------------------------- 40ºC.
Soil temperature--------------------------------------------------  -------------25ºC.
Soil thermal resitivity-------------------------------------------------------------1.0ºCm/w
Buried depth--------------------------------------------------------------------------0.8m
Single-Circuit only
Single-core cable is installed in parallel.Adjacent space is equivalent to the diameter of the cable.
Correction factors of current carrying for different soil temperature
Soil temperature(ºC)15202530354045
Rating factor1.091.041.00.960.920.870.83
Correction factors of current carrying for different thermal temperature
Rating factors for soil Thermal resistivityºC.m/w1.01.21.52.02.53.03.5
Three cores1.00.9430.8770.7920.7360.6750.641
Single core1.00.9340.8500.7480.6920.6350.598
Correction factors of current carrying for different air temperature
Air temperature(ºC)20253035404550
Correction factor1.181.141.101.051.00.950.89
 
Prod Model: CU/XLPE Insulation/Steel Wire Armoured/PVC
Markets: North America,South America,Eastern Europe,Southeast Asia,Africa,Oceania,Mid East,Eastern Asia,Western Europe
Rated Voltage: 18/20kv,18/30kv
Size: 25-630mm2
No. Of Cores: 1 or 3
Armoured Layer: Steel Wire
Application: Power Station
Voltage: High Voltage Cable
Current: DC & AC
Insulation Material: XLPE
Certification: CE
Model: Cu/XLPE Insulation/Steel Wire Armoured/PVC
Brand: Lonheo
Established in 2014 and bringing together the factory more than 30 years of experience in cable, Lonheo is backed by the excellent reputation of our cooperated factory, All what we do is to make them as leading cable contractors in the world.

Lonheo is able to strive in today's competitive business environment by creating synergy and consolidating the resources of all partners. This ensures that Lonheo remains operationally and financially strong.

With this strategic partnership in place, Lonheo is able to help our customers achieve their goals and provide greater value-added services to them.

Our company are focus on cable & wire supplyment and waste water treatment chemicals.

Our Features Product:

===Power Cables===

Ultra High Voltage, Power Cable, High Voltage Power Cable, Medium Voltage Power Cable, Low Voltage Power Cable, LSZH (low smoke zero halogen) Cable, XLPE Cable, AAAC (Aluminium Alloy Conductor) Power Cable, Armoured Cable, SWA (Steel Wire Armoured) Cable.

Power cables are mainly used for power transmission and distribution systems in the power industry and general industries.

===Wires and cables for electrical equipment===

Rubber Insulated Cable, Mining, Drilling & Tunnelling Cable, Ship Cable, Nylon Sheathed Wire, Plastic Insulated Control Cable.

Electrical Equipment Cables are mainly used to supply and distribute electricity.

===Aerial Cable===

Aerial Bundled Cable, Copper Stranded Wire, Aluminium Conductor Steel Reinforced (ACSR) Wires, Aluminium Alloy Conductors (AAAC), Aluminium Stranded Conductor (AAC).

These cables are mainly used as overhead power lines for power transmission and power distribution.

===Special Cables and Wires===

Fire Resistant Cable, High Temperature Resistant Cable, Rodent Resistant Cable / Termite Resistant Cable, Waterproof Cable, Eco-friendly Direct Current cable, Medium Voltage Power Cable for Subway and Light-weight, Wind Energy Cable, 1E Class Nuclear Cable, Energy Efficient ACSR, UHV Supporting and Expanding Overhead Wires, Flexible Fire-proof Cable for 0.6/1KV.

Send your message to this manufacturer

  • Wuxi Lonheo International Trade Co., Ltd.

More >

Other Products From This Manufacturer