FC-043 LED digital refrigerator temperature controller is a new mode of system control especially for the cold storage, refrigerated counters. To better monitor the intelligent controller by more advanced system, including fan delay in the controller, always open, to start and stop at the same time, entering setting of defrost temperature, the water drop time after defrost, optional defrost mode (electrical defrost), defrosting exit protected by temperature and time to prevent overheat testing. The entry and exit of one-touch mandatory defrost can check the remaining time of operation. Self-signal switch detection, fault self-test function of sensor. The simple operation and full range of functions make the users gain better application.
FC-043 LED digital refrigerator temperature controller Technical specification:
1. Input type: 2×NTC5K (-50~50oC)
2. Resolution: 1oC, Accuracy: ±1oC
3. Contact capacity: Cooling control 10A 250VAC;
Defrosting and Fan control 5A 250VAC
4. External dimensions (mm): 77(W)×35(H)×62(D) hole dimensions: 71(W)×29(H)
5. Working power: AC110V242V,50/60HZ, power dissipation is less than 3W
6. Working environmenttemperature: -20~50oC, relative humidity ≤ 85%RH, without corrode and strong electric radiation.
The inner parameters
Code | Name | Range | Note | Factory setting |
| Setting temperature | -50~50ºC | Compressor stops when the temperature reach the setting value. Please refer to "4.2,Temperature setting" and "5.1 Cooling Output" | -10 |
F0 | Temperature difference | 1~15ºC | Please refer to "5.1 Cooling Output" | 3 |
F1 | Defrosting cycle | 1~24Hrs | Interval time between the two defrosting. | 12 |
F2 | Defrosting time | 1~45Min | Working time of defrosting | 15 |
F3 | Temperature correction | -15~15ºC | To use this function when there is deviation between the actual temperature and displaying temperature | 0 |
F4 | Delay time | 1~5 Min | Delay time before starting of compressor | 2 |
F5 | Exit defrosting temperature | 5~35ºC | Defrosting end temperature when defrosting | 5 |
F6 | Entering defrosting temperature | 5~-35ºC | Temperature conditions of entering defrosting | 5 |
F7 | Fan mode | -1~5 | Fan runs ahead when set -1, Fan runs or stops at the same time with compressor when set 0, 1~5 is for delaying start, delaying stop. | 0 |
F8 | Water drop time | 0~10Min | Water drop time after every defrosting end | 5 |
F9 | Defrosting mode | 0~1 | Please refer to "5.5,Defrosting mode" | 0 |
Yuyao Gongyi Meter Co., Ltd And Its Subsidiary, Yuyao Changjiang Temperature Meter
Factory, Have Been Devoting Themselves To The Development And manufacturing Of
Industrial Process Automation Controller Instruments Since 1995. Through Decades Of
Improvement, Gongyi Now Is A Top One Chinese Instrument Manufacturer, Claiming A
Large Domestic And Overseas Market Share, sales of CJ temperature controller.
Main products: Temperature controller, humidity controller, electrical instrument, time relay, paperless recorder, silicon-controller, voltage regulator and all kinds of temperature sensor, humidity sensor, temperature transmitter and safety barrier. All the instruments have the function to communicate with computer, and provide the computer industrial control interface. (DCS System)
"CJ" series Temperature Meter has been ISO9001-2008 quality system' S grant, CE and kinds of certification, and has international facture calculate appliance' S license ( CMC 02810232 )
Welcome to our factory.