Photoelectric heat detector fire alarms
Features and Technical parameters
1. Work indication: The red indicator will blink in the monitoring status or remain lit in the alarm status.
2. Weight: About 47g
3. Product class: A2
4. External dimensions: Diameter: 100mm, height: 56mm (with the base)
5. Wiring method: Non-polarity two-bus system (L1, L2)
6. Operating environment: Indoor, temperature: -10° C~+50° C; Relative humidity: ≤ 95% (40° C± 2° C, without condensation)
7. Coding mode: It can realize electronic coding via coder in situ. Address codes 1 to 324 are available for selection.
8. Installation height: ≤ 8m
9. Protection area: About 60m2. For details, see related provisions in GB50116-98 Code for Design of Automatic Fire Alarm System.
10. Matched host machine: Fire alarm control panel (such as AW-AFP2188)
Asenware sets up in 2006, the predecessor is Shenzhen Widesense Technology Co., Ltd. Now Asenware is an international group company.
We are a technology-oriented company that devotes to NDT (Non Destructive Test) and BMS (Building Management System) industries.
We have two factories: One factory is in Shenzhen city for BMS products, and another is in Dandong city for NDT X-ray products.
In our BMS factory, we produce addressable and conventional fire alarm system, CCTV camera and DDC controller.
In our NDT X-ray factory, we produce portable and mobile NDT X-ray flaw detectors, X-ray analysis equipment and the dark room accessories.
We have an experienced R&D team to design special electrical product for test and control usage.
We have been striving to provide customers with satisfying service before, during and after sales.