DNK (Xiamen) Electrical Co., Ltd >> High Voltage Electric 11kv Circuit Breaker

High Voltage Electric 11kv Circuit Breaker

High Voltage Electric 11kv Circuit Breaker
Price: US $ 1/Piece
Trade Terms: FOB
Min Order: 1/Piece
Pay Type: T/T

Product Specifications

Prod Model: VSB1-12(24)
Markets: North America,South America,Eastern Europe,Southeast Asia,Africa,Oceania,Mid East,Eastern Asia,Western Europe
Rated Voltage: 11kv
Rated Current: 630A
1 Min Frequency Withstand: 42/49kv(Phase to Phase,Phase to Earth/Across Isola
1 Min Frequency Withstand.: 34kv(Phase to Earth,External Insulation)
Lightning Impulse Withstand Voltage: 75/85kv(P to P,P to E/Across Isolating Distance
Rated Frequency: 50Hz
Rated Short-Circuit Breaking Current: 20ka,25ka
Rated Peak Withstand Current: 50ka,63ka
Rated Operating Voltage: 220V
Model: High Voltage Electric 11kv Circuit Breaker
Arc-extinguishing Medium: Vacuum
Breaking Capacity: High Voltage Circuit Breakers
Poles Number: 3
Certification: ISO9001-2000
Operation: Manual Type
Installation: Fixed
Speed: High-Speed Circuit Breaker

Product Description

High Voltage Electric 11kV Circuit Breaker

Description & Application
High voltage 11kv circuit breaker is composed of outdoor pole-mounted vacuum circuit breaker, fault detector and outer voltage transformer, which are electrically connected with each other by aviation socket and outdoor sealing cable. With functions of fault detecting, protecting & controlling and communication, it can examine the mA-level of zero-sequence current and the fault current of phase to phase short-circuit, then automatically cut off the single phase earthing fault and phase short-circuit fault.

Current Transformer Assembly
Each phase (Phase A, Phase C) in circuit breaker is installed 1pc current transformer for phase protection, the transformation ratio is 50~600/1.

Zero-sequence Current Transformer
1PC zero-sequence current transformer is installed in circuit breaker, the transformation ratio is 20/1. It should keep linear relationship during 0.2~6A, the transformation ratio deviation should be lower than 3% on condition of rated load. When the zero-sequence current is 400A the second time output current should be no less than 6A.

Operation Power Supply
1) Circuit breaker needs operating power when working. The operating power can be through AC 220V or DC 20V power (Voltage should be the same with power supply of controller), but it usually gets AC 220V power by installing a voltage transformer in 10kV line.
2) The external operating voltage transformer can be selected by user, for convenient installation the outdoor item with fuse is priority choice. If choose non-fuse item, an outdoor fuse shall be installed additionally for power transformer protection.

Watchdog
If install a power accept circuit breaker (usually called" watchdog") at the responsible point of branch line or terminal user, it will judge the fault (over current, short-circuit, single phase earthing, etc. ), automatically disconnect it, and keep normal electric power for non-fault users, suitable for incoming T connection or terminal connection as well as other satisfactory branch connecting positions.

Application Conditions
1 Ambient Temperature: -40° C~+40° C, Daily range of temperature: ≤ 25° C
2 Max Wind Speed: ≤ 35m/s
3 Application Site: No danger of inflammable, explosion hazard, strong chemical corrosion (such as acid, alkali or fume etc. ) and violent vibration
4 Elevation: ≤ 1000m (If beyond 1000m, should reconfirm with manufacturer)
5 Thickness of Covering Ice: ≤ 10mm
6 Class of Air Pollution: Level 4
7 Seismic Intensity: ≤ 8
7 Neutral Point Earthing Method: Ungrounded, grounded through arc extinction coil, grounded by small resistance.

Standards
Electric Circuit Breaker Series
DL/T403
GB1984
GB311.1
GB3309
GB4208
GB/T11022
DL/T593
DL/T884
DL/T615
GB8905
GB50150

Service
Shipping
1 Sea Way
2 Air Way
3 Express

Payment
1 PayPal
2 West Union
3 Wire Transfer
4 T/T

If you have interest in our high voltage 11kv circuit breaker, please feel free to contact us.
DNK (Xiamen) Electrical Co., Ltd is a professional electrical manufacturer which was established in 2008 and invested by U. S. A. DNK Electrical Industry Corporation. We are specialized in 0.4kV-1000kV DNK-branded outdoor electric power equipment. The product included disconnector switch, dropout fuse cutout, circuit breaker, load break switch, ring main unit, fuse link and so on.

If you have any interest in our company or any items, pls feel free to contact us. We are always at your service.

Send your message to this supplier

  • DNK (Xiamen) Electrical Co., Ltd

Other Products From This Manufacturer