Categories
Price: | US $ 1/Piece |
---|---|
Trade Terms: | FOB,CFR,CIF |
Min Order: | 1/Piece |
Pay Type: | L/C,T/T |
Model | EKCW200AA | EKCW300AA | EKCW400AA | EKCW500AA | EKCW600AA | EKCW800AA | EKCW1000AA | EKCW1200AA | EKCW1400AA | ||
Rated air flow (m3/h; under static pressure of 12Pa, 30Pa and 50Pa) | H | 340 | 510 | 680 | 850 | 1020 | 1360 | 1700 | 2040 | 2380 | |
M | 279 | 418 | 558 | 697 | 836 | 1115 | 1394 | 1673 | 1952 | ||
L | 170 | 255 | 340 | 425 | 510 | 680 | 850 | 1020 | 1190 | ||
Rated cooling capacity (W) | Total heating/cooling capacity | H | 2125 | 3385 | 4390 | 4902 | 6207 | 8096 | 10165 | 11066 | 13744 |
Sensible heating/cooling capacity | H | 1233 | 2059 | 2848 | 3353 | 4179 | 5572 | 7125 | 7961 | 9770 | |
Rated heating capacity (W) | H | 3576 | 5427 | 6915 | 8335 | 12238 | 13216 | 16587 | 18339 | 22160 | |
Rated input power (W) | Static pressure of 12Pa | H | 32 | 46 | 56 | 73 | 93 | 133 | 164 | 188 | 229 |
Static pressure of 30Pa | H | 41 | 53 | 72 | 86 | 107 | 142 | 183 | 217 | 239 | |
Static pressure of 50Pa | H | 46 | 65 | 77 | 90 | 115 | 162 | 187 | 227 | 279 | |
Working current (A) | Static pressure of 12Pa | H | 0.15 | 0.21 | 0.26 | 0.33 | 0.42 | 0.61 | 0.74 | 0.85 | 1.04 |
Static pressure of 30Pa | H | 0.2 | 0.24 | 0.33 | 0.39 | 0.48 | 0.65 | 0.83 | 0.99 | 1.09 | |
Static pressure of 50Pa | H | 0.21 | 0.29 | 0.35 | 0.41 | 0.52 | 0.74 | 0.85 | 1.03 | 1.27 | |
Sound dB(A) | Static pressure of 12Pa | H | 33.5 | 32.5 | 38.5 | 41.5 | 44.5 | 45 | 48 | 49 | 51 |
Static pressure of 30Pa | H | 39.5 | 40 | 43 | 44 | 46 | 46 | 50.5 | 50.5 | 51.5 | |
Static pressure of 50Pa | H | 42 | 43 | 45 | 46 | 47.5 | 48.5 | 50.5 | 52.5 | 53 | |
Water flow | m³/h | 0.21 | 0.33 | 0.43 | 0.48 | 0.6 | 0.79 | 0.99 | 1.07 | 1.32 | |
Water resistance (cooling) | kPa | 5 | 13 | 22 | 10 | 16 | 16 | 25 | 20 | 29 | |
Water resistance (heating) | kPa | 4 | 9 | 18 | 8 | 13 | 13 | 20 | 17 | 24 | |
Coil | Type | Mechanically expanded quality copper tubes specially designed for air conditioners with shutter-type hyperbolic aluminum fins | |||||||||
Working pressure | 1.6MPa | ||||||||||
Test pressure | Airtightness test under pressurized water: 3.3 Mpa | ||||||||||
Fan | Type | Forward-pitched multi-wing centrifugal fan with double-suction impellers made from zinc-plated steel plates | |||||||||
Q'ty | 1 | 2 | 2 | 2 | 2 | 3 | 4 | 4 | 4 | ||
Motor | Type | Single-phase ball-bearing capacitive motor with a high precision and low operation sound | |||||||||
Q'ty | 1 | 1 | 1 | 1 | 1 | 2 | 2 | 2 | 2 | ||
Power supply | 220/1/50 | ||||||||||
Protection grade | IP20 | ||||||||||
Insulation grade | B | ||||||||||
Inlet/outlet water pipe | Pipe diameter | Rc3/4 taper pipe with internal thread | |||||||||
Condensate water pipe | Pipe diameter | Diameter R 3/4 taper pipe with external threads | |||||||||
Net weight (no electric heater) | No return air plenum | kg | 11.8 | 14.3 | 16.8 | 17.9 | 19.1 | 28.4 | 31.4 | 34.3 | 41.3 |
With return air plenum | kg | 14.8 | 17.9 | 20.8 | 22.2 | 23.7 | 34.4 | 37.8 | 41.5 | 49.5 | |
Electric heater (optional) | Power supply | 220/1/50 | 380/3/50 | ||||||||
Electric heating capacity | kw | 1/2 | 1/2/3 | 2/3/4 | 2/3/4 | 2/3/4 | 3/4/5 | 3/4/5 | 4/5/6 | 5/6/7 | |
Net weight (with electric heater) | No return air plenum | kg | 14.9 | 17.5 | 20.5 | 21.8 | 23.2 | 33.4 | 36.6 | 40.1 | 47.8 |
With return air plenum | kg | 17.9 | 21.1 | 24.5 | 26.1 | 27.8 | 39.4 | 43 | 47.3 | 56 | |
Note: 1. Working conditions for cooling: inlet air temperature - dry/wet bulb 27°C/19.5°C; temperature of inlet/outlet water - 5°C/15°C. 2. Working conditions for heating: inlet air temperature - dry bulb 21°C; inlet water temperature 60°C; water flow - equal to that for cooling operation. 3. Rated air flow is measured under standard atmosphere using dry coils (dry bulb 20°C). 4. Sound pressure grade and sound level are measured in a semi-silent room as per GB/T 19232-2003. 5. H, M and L represent high, medium and low fan speed respectively. 6. Static pressure refers to outlet static pressure. 7. All performance parameters in the above table are measure with a power supply of 220V~/50Hz. 8. The right/left orientation of connection pipes are exchangeable on site (cooling/heating capacity needs to be multiplied by a correction factor of 0.93 after exchange). |
Markets: | North America,South America,Eastern Europe,Southeast Asia,Africa,Oceania,Mid East,Eastern Asia,Western Europe |
---|