Zhejiang Cen New Energy Technology Co., Ltd. >> Water/Ground Source Heat Pump for Cooling, Heating and Hot Water -20kw

Water/Ground Source Heat Pump for Cooling, Heating and Hot Water -20kw

Water/Ground Source Heat Pump for Cooling, Heating and Hot Water -20kw
Price: US $ 1850/Piece
Trade Terms: FOB,CIF,EXW
Min Order: 2/Piece
Pay Type: L/C,T/T

Product Specifications

Prod Model: CSGRS-20II
Markets: North America,South America,Eastern Europe,Southeast Asia,Africa,Oceania,Mid East,Eastern Asia,Western Europe
Product Name: Ground Source Heat Pump for Cooling & Heating and
Refrigerant: R410A
Compressor: SANYO
Rated Heating Capacity: 4.3kw
Cooling Capacity: 4kw
Hot Water Heating Capacity: 4.8kw
Heat Source: Ground-source
Certification: CCC
Work Environment: Common Heat Pump
Heat Temperature: 50-70??C
Application: Villa Family

Product Description

Application

A. Application of the conditions of groundwater source heat pump system
1. Rich water near the building, facilitate the implementatiom of the supply and return water
2. Local policy allows using groundwater
3. Groundwater temperature appropriate, the water is suitable, water supply stability, water return smoothly

B. Application of the conditions of the surface water source heat pump system
1. Rich water near the building ( such as river, lake water, seawater, reservoir water, industrialwastewater and so on)
2. Adequate water, moderate temperature, the water can meet the using requirements after simple handling.
C. Pplication of the conditions of ground source heat heat pump system
1. Lake of water near the building or various factors limit use of water resource
2. There is enough space around the building for the ground-couple system.

Advantages

1. High Reliability

Using famous parts, and as the temperature of the original source is stable, the water/ground source heat pump works more reliable and stable, guaranteeing the high efficiency and economy. Without problem of defrosting in winter.

2. One Unit for Multi-usage and Wide Application

It could be used for cooling, heating and tap hot water for daily life, one unit for multi-usage.

3. High Efficiency for Heat Recovery

Using the latest high technology, following the law of conservation, when the unit is cooling, the heat recovers to produce the hot water (for example, in summer, it provides the free hot water by heat recovery). The unit is with higher efficiency and more energy saving.

4. Less Cost

The working condition is reliable, so the system is simple and less components. It runs easily and reliably, and maintenance cost is less.

5. Environment Friendly

Use R410A refrigerant, the ratio of ozonosphere damage is zero, environment friendly, green product, meet the countries' environmental protection demand.
Water/Ground Source Heat Pump combines Cooling, Heating and Hot Water Production (heat recovery)
Parameters   CSGRS-4I   CSGRS-8I CSGRS-12II CSGRS-20II   CSGRS-40II
Hereunder is the testing result under standard conditions:                                                                                                                                                                                                                                         (1)    standard cooling conditions: application side water inlet temperature 12, water outlet temperature 7; source side water inlet temperature 15, water outlet temperature 20.                                                                                                                                                                                                                             (2)    standard heating conditions: application side water inlet temperature 40, water outlet temperature 45; source side water inlet temperature 15, water outlet temperature 10.  
Cooling Capacity kW 4 8 12 20 40
Heating Capacity kW 4.3 8.6 13 22 45
Hot Water Heating Capacity (entire heat recovery ) kW 4.8 9.5 14.5 23.5 48.5
input power for cooling kW 0.8 1.6 2.5 4.1 8.3
input power for heating kW 0.95 1.9 2.8 4.7 10.2
input current for cooling A 4.2 8.4 4.5 7.6 15.2
input current for heating A 5.1 10.2 5.3 8.7 18.2
Hereunder is the testing result in underground water norminal conditions:                                                                                                                                                                                                                           (1)      underground water norminal cooling conditions:                                                                                                                                                                                                                                                                 application side water inlet temperature 12,   water outlet temperature 7;                                                                                                                                                                                                                                                                                                                           source side water inlet temperature 18, water outlet temperature 29.                                                                                                                                                                                                                                                                                                                               (2)      underground water norminal heating conditions: application side water inlet temperature 40, water outlet temperature 45; source side water inlet temperature 15, water outlet temperature 7.
underground water norminal conditions Cooling Capacity kW 3.9 7.7 11.5 19.5 38.4
Heating Capacity kW 4.2 8.2 12.5 21.2 43.2
Hot Water Heating Capacity (entire heat recovery ) kW 4.5 9.1 13.5 23.3 47.5
input power for cooling kW 0.81 1.6 2.6 4.1 8.2
input power for heating kW 0.93 1.8 2.7 4.8 9.8
input current for cooling A 4.4 8.5 5 7.7 15.3
input current for heating A 4.8 10.2 5.1 9.1 18
  Hereunder is the testing result in ground source closed loop norminal conditions:                                                                                                                                                                                                                           (1)      ground source closed loop norminal cooling conditions: application side water inlet temperature 12, water outlet                    temperature 7; source side water inlet temperature 25, water outlet temperature 30.                                                                                                                                                                                                                             (2)      ground source closed loop norminal heating conditions: application side water inlet temperature 40, water outlet temperature 45; source side water inlet temperature 10, water outlet temperature 5.
ground source closed loop norminal conditions Cooling Capacity kW 3.8 7.6 11.4 19.1 38
Heating Capacity kW 4.1 8.1 12.3 20.9 42
Hot Water Heating Capacity (entire heat recovery ) kW 4.4 8.9 13.2 22.5 46.2
input power for cooling kW 0.8 1.6 2.5 4.2 8.4
input power for heating kW 1.1 2.1 3.1 5.1 10.5
input current for cooling A 4.2 8.4 4.7 7.9 15.6
input current for heating A 5.7 11.1 5.8 9.6 19
  Hereunder is the testing result in water loop norminal conditions:                                                                                                                                                                                                                           (1)      water loop norminal cooling conditions: application side water inlet temperature 12, water outlet temperature 7; source side water inlet temperature 30, water outlet temperature 35.                                                                                                                                                                                                                             (2)      water loop norminal heating conditions: application side water inlet temperature 40, water outlet temperature 45; source side water inlet temperature 20, water outlet temperature 15.  
water loop conditions  Cooling Capacity kW 3.6 7.2 10.9 18.1 36.2
Heating Capacity kW 4.7 10.3 15.6 26.4 54.6
Hot Water Heating Capacity (entire heat recovery ) kW 5.1 11.3 17.1 29.1 60
input power for cooling kW 0.97 1.9 2.9 4.9 9.5
input power for heating kW 1.05 2.3 3.5 6 12.1
input current for cooling A 5.1 10.3 5.6 9.2 17.6
input current for heating A 5.5 12.3 6.7 11 22.5
Power Supply 220V/50Hz 380V/50Hz
Compressor Type Rotor Type Scroll Type
quantity pc 1 1 1 1 2
energy adjust % 0, 100 0, 100 0, 100 0, 100 0, 50, 100
 
source side heat exchanger    type plate-type heat exchanger
water flow in underground water type  cooling condition m 3 /h 0.36 0.7 1.1 1.8 3.6
water flow in underground water type  heating condition m 3 /h 0.42 0.83 1.3 2.1 4.2
water flow in ground closed loop and water loop cooling condition m 3 /h 0.7 1.4 2.2 3.6 7.2
water flow in ground closed loop and water loop heating condition m 3 /h 0.66 1.31 1.96 3.3 6.6
Water Pressure Drop kPa < 30 < 50
pipe size mm DN20 DN20 DN20 DN25 DN40
 
application side heat exchanger type plate-type heat exchanger
water flow during cooling m3/h 0.69 1.38 2.1 3.5 6.9
water flow during heating m3/h 0.7 1.4 2.3 3.8 7.7
Water Pressure Drop kPa < 30 < 40
pipe size mm DN20 DN20 DN20 DN25 DN40
 
hot water side heat exchanger type efficient shell and tube heat exchanger
water flow during heating m3/h 0.82 1.6 2.4 4 8.2
Water Pressure Drop kPa < 30 < 50
pipe size mm DN20 DN20 DN20 DN25 DN40
Protection high pressure and low pressure protection, anti-freezing protection, high temperature protection, safety valve, overload protection, lack phase protection, reverse phase protection, water flow protection ect.  
refrigerant type R410A
Throttle Type   thermostatic expansion valve
quantity kg 0.9 1.3 2.1 3.2 3.5× 2
unit dimensions Length mm 900 900 956 956 1315
Width mm 510 510 556 556 765
Height mm 600 600 680 680 1045
Noise ≤ dB(A) 35 48 52 54 61
Weight kg 52 65 75 125 290
Remarks:                
1, Hot water side initial water temperature 15, outlet water temperature 55.  
2, The product parameters may have some difference from the final product because of products updating, please refer to               
    final product label when buy. Our company keeps the right to interpret.              
Zhejiang Cen New Energy Technology Co., Ltd. Our company is still developing more styles of products. We take the technology as the core\regard the quality as life\treat the user as god. We dedicated to provide you with the highest cost-effective energy-saving products\high-quality engineering design and meticulous transformation of after-sales service!

Our main products as follows:
Air-source heat pump unit for household and commercial
Ground source heat pump unit
Water source heat pump unit
Combine cooling\heating and hot water heat pump unit
Swimming pool heat pump unit
Heat recovery of centre air-conditioner so on energy-saving products, our products passed prove ISO9001\CCC\CE certificate.
Product features: Reasonable structure\stable quality\reliable and nice.

We consistently insist on the sane business strategy. We don't demand the biggest, only best. Take the most serious attitude, do the most professional thing. Let us enhance friendship with large clients and sincere cooperation, create brilliance!

Send your message to this supplier