Dry transformer performance is up to IEC726, GB6450, GB/T10228-1997 Standard.
The transformer owns its advantage such as low loss and noise, small size, less weight, moisture-proof, anti-dirty, crack-proof, withstanding impulse, flameproof, overload capability, smaller partial discharge (less than 10 PC).
Feature:
Adopting advanced technology and high quality raw material, with first class equipment and strict processing, SC-series resin casting dry type transformer owns the following advantages:
1. Copper conductor is used both for H. V. &L. V. Coils to strengthen the glass fiber. It is dried and cast by epoxy resin under the high vacuum. After curing, it is a firm cylinder, with high mechanical strength and withstanding short-circuit capability, smaller partial discharge, higher reliability as well as long service life.
2. Flameproof, explosion resistant, no pollution to environment. Because the imported epoxy resin and glass fiber compound insulation materials are used and certain silicon powder is contained in the epoxy resin. Heat conduction co-efficient and flameproof ability is greatly improved in comparison with old type materials. There would be no toxin and harmful gas caused by resin under high temperature.
3. The moist cannot be absorbed by coils. The core clamp is coated with the special anti-corrosive materials so it can do as usual under the severe conditions. It is unnecessary to get rid of moisture for interval operation.
4. Good capabilities of withstanding short-circuit and lightning impulse.
5. Good heating dissipation due to thin resin coated on the outside of coils. Normally, natural air cooling (AN) is taken. Fan cooling system could be provided with the transformer in any protection grade to improve short time overload ability and ensure the safe operation.
6. Low loss and noise, energy saving, economical operation, free from maintenance.
7. Small size, less weight, little occupied area, and few cost for installation. It is unnecessary to take consideration of drainage pool, fire proof and fire fighting facilities, as well as standby power source.
8. Without any risk of fire disaster, explosion, it could also be installed separately around loading center, close to electric consuming place, so the wiring costs can be reduced and more costs can be saved.
Technical parameter:
Voltage class: 6 -35KV
Capacity range: 30 - 10000kVA
Voltage adjustment mode: No-load tap changer or on-load tap changer (fitted with vacuum or on-load tap changer )
Tapping range: +/- 2X2.5% +/- 4X2.5% (or others)
Frequency: 50Hz or 60Hz
Phase number: Three phase
Vector group: Yyn0; Dyn11; Yd11 or others
Short-circuit impedance: Standard impedance ( requirement by customer)
Working condition: Relative humidity 100%, ambient temperature no more than 40 degrees centigrade
Max. Temperature rise: 100K
Cooling mode: Natural air cooling (AN) or fan cooling (AF)
Protection grade: IP00; IP20(indoor ); IP23(outdoor)
Insulation grade: F grade
Insulation level:
10KV Power frequency withstanding voltage 35KV, impulse withstanding voltage 75KV;
20KV Power frequency withstanding voltage 50KV, impulse withstanding voltage 125KV;
35KV Power frequency withstanding voltage 70KV, impulse withstanding voltage 170KV.
Technical Parameter for SC (B ) 9 Series |
H -V : 10(10.5,11,6,6.3,6.6)±2X2.5%kV Vector Group: Y,yn0 or D,yn11 |
L -V : 0.4kV Insulating Level: LI75AC35/LI0AC3 |
Model | Po | Pk (120C) | Uk | Io | Sound Level | Dimension(main body) |
W | W | % | % | dB(A) | L X W X H X Track |
SC9-30/10 | 200 | 745 | 4 | 2.2 | 43 | 700X460X750X400 |
SC9-50/10 | 300 | 1050 | 4 | 2.0 | 43 | 945X750X950X550 |
SC9-80/10 | 380 | 1450 | 4 | 1.8 | 43 | 945X750X945X550 |
SC9-100/10 | 430 | 1660 | 4 | 1.8 | 44 | 945X750X965X550 |
SC9-125/10 | 520 | 1950 | 4 | 1.6 | 44 | 1040X860X1045X660 |
SC9-160/10 | 600 | 2250 | 4 | 1.4 | 44 | 1040X860X1085X660 |
SC9-200/10 | 700 | 2670 | 4 | 1.4 | 45 | 1040X860X1115X660 |
SC9-250/10 | 800 | 2800 | 4 | 1.4 | 45 | 1170X860X1120X660 |
SC9-315/10 | 940 | 3660 | 4 | 1.2 | 47 | 1240X760X1305X660 |
SCB9-400/10 | 960 | 4210 | 4 | 1.2 | 48 | 1320X760X1390X660 |
SCB9-500/10 | 1150 | 5150 | 4 | 1.2 | 48 | 1360X760X1455X660 |
SCB9-630/10 | 1320 | 6180 | 4 | 1.0 | 50 | 1460X760X1500X660 |
SCB9-630/10 | 1280 | 6300 | 6 | 1.0 | 50 | 1460X760X1480X660 |
SCB9-800/10 | 1500 | 7330 | 6 | 1.0 | 52 | 1520X920X1590X820 |
SCB9-1000/10 | 1760 | 8590 | 6 | 0.8 | 54 | 1600X920X1720X820 |
SCB9-1250/10 | 2060 | 10190 | 6 | 0.8 | 54 | 1660X920X1895X820 |
SCB9-1600/10 | 2400 | 12370 | 6 | 0.8 | 56 | 1800X920X1985X820 |
SCB9-2000/10 | 3200 | 15230 | 6 | 0.6 | 57 | 1800X920X2135X820 |
SCB9-2500/10 | 3800 | 18090 | 6 | 0.6 | 57 | 2070X1170X2180X1070 |
Technical Parameter for SC (B) 10 Series |
H- V: 10(10.5,11,6,6.3,6.6)±2X2.5%kV Vector Group: Y,yn0 or D,yn11 L- V: 0.4kV Insulating Level: LI75AC35/LI0AC3 |
Model | Po W | Pk (120 C) W | Uk % | Io % | Soud LEVEL dB(A) | Dimension(main body) L X W X H X Track
|
SC10-30/10 | 200 | 700 | 4 | 2.2 | 43 | 700X460X750X400 |
SC10-50/10 | 285 | 985 | 4 | 2.0 | 43 | 945X750X950X550 |
SC10-80/10 | 365 | 1375 | 4 | 1.8 | 43 | 945X750X945X550 |
SC10-100/10 | 405 | 1570 | 4 | 1.8 | 44 | 945X750X965X550 |
SC10-125/10 | 480 | 1830 | 4 | 1.6 | 44 | 1040X860X1045X660 |
SC10-160/10 | 560 | 2120 | 4 | 1.4 | 44 | 1040X860X1085X660 |
SC10-200/10 | 650 | 2520 | 4 | 1.4 | 45 | 1040X860X1115X660 |
SC10-250/10 | 760 | 2750 | 4 | 1.4 | 45 | 1170X860X1120X660 |
SC10-315/10 | 880 | 3455 | 4 | 1.2 | 47 | 1240X760X1305X660 |
SCB10-400/10 | 960 | 3985 | 4 | 1.2 | 48 | 1320X760X1390X660 |
SCB10-500/10 | 1150 | 4875 | 4 | 1.2 | 48 | 1360X760X1455X660 |
SCB10-630/10 | 1320 | 5870 | 4 | 1.0 | 50 | 1460X760X1500X660 |
SCB10-630/10 | 1280 | 5950 | 6 | 1.0 | 50 | 1460X760X1480X660 |
SCB10-800/10 | 1500 | 6950 | 6 | 1.0 | 52 | 1520X920X1590X820 |
SCB10-1000/10 | 1760 | 8120 | 6 | 0.8 | 54 | 1600X920X1720X820 |
SCB10-1250/10 | 2060 | 9685 | 6 | 0.8 | 54 | 1660X920X1895X820 |
SCB10-1600/10 | 2400 | 11720 | 6 | 0.7 | 55 | 1800X920X1985X820 |
SCB10-2000/10 | 3200 | 14430 | 6 | 0.5 | 55 | 1800X920X2135X820 |
SCB10-2500/10 | 3800 | 17060 | 6 | 0.5 | 56 | 2070X1170X2180X1070 |
Ningbo Ville Electric Co., Ltd. is a company specialized in research, development and production of transformer and high voltage & low voltage electrical power equipment.
It locates in Hi-technical enterprise R & D center zone of Ningbo, Zhejiang province, which is one of the well-know coastal city in China. Its professional engaged in turnkey project contractor of power substation, power plant project and electric power complete equipments.
Working field: Manufacturing, engineering, designing, executing and commissioning for HV and LV electrical products.
Products application:
Power-fossil fuel plant, Steel plant, Infrastructure- railway, international generation, substation, hydropower station, wind power substation, transmission and distribution.
We has excellent experience and good capacity in complete projects equipments in Generation, Substation, Transmission and Distribution from 400V-330kv, especially in Power plant, Substation construction and Transmission line, including of design, complete equipment, installation, Commissioningand after-sales service, and also design the complete Electrical Solutions according to customer's demand. We are mainly services to International State Power Board, Power Construction Contractor, Power Project Contractor, Factories and the Electric Power Project in the world.
In order to achieve the enterprise's strategic target---being stronger, larger, and superior, we continue to expand throughout the world's markets for power transmission and distribution area. And we also actively attach our team to competition, walking forward to the mission of "First-class worldwide electrical equipment supplier"