Categories
Supplier: | Shenzhen Asenware Test and Control Technology Co., Ltd. |
---|---|
Price: | US $ 270/Piece |
Min Order: | 1/Piece |
Quantity:: | |
Trade Terms: | FOB,EXW,CIF |
![]() |
Prod Model: | AW-CFP2166-24 |
---|---|
Markets: | North America,South America,Eastern Europe,Southeast Asia,Africa,Oceania,Mid East,Eastern Asia,Western Europe |
Optional Zone Capacity: | 1-32 |
Power Supply: | 240VAC |
Backup Battery: | 24VDC |
Fire Detector: | Photoelectric Smoke Detector |
Temperature Alarm: | Thermal Resistor Heat Detector |
Wire System: | 2-Wire System |
Exterior Housing: | Weather-Proof Painted Metal Shell |
PCB Board Circuit: | SMT Process |
Optional Panel Color: | Red/Grey/Black/White |
Warranty & Maintenance: | 12 Months & Lifetime |
Alarm Volume (',within 1m): | ≥100dB |
Transmission Mode: | Cable |
Certification: | CCC |
Type: | Industry Alarm |
Application: | Fire Project |
Signal Transmission: | Wired Alarm |
Working Mode: | Active |
Sensor Type: | Electric Alarm |
Usage: | Factory/Hotel/School/Office Fire Alarm Control |
Receive Frequency: | Wire |
Working Principle: | Response to The Trigger Device |
ITEM | 1Zone panel | 2Zone panel | 4-8 Zone panel | 12-32 Zone panel |
Model No. | AW-CFP2166-01 | AW-CFP2166-02 | AW-CFP2166-04-8 | AW-CFP2166-12-32 |
Power specification |
|
|||
Mains supply voltage | 110VAC or 240VAC | |||
Internal power supply | 27.2VDC | |||
Total output current limited | 500mA @ 240VAC | 500mA @ 240VAC | 3A @ 240VAC | 3A @ 240VAC |
Main supply monitor for fault | Yes | |||
Battery protection for low voltage | Yes | |||
Batteries (default configuration) | 12V2AH*2 | |||
Detector circuit specification |
|
|||
Number of circuit | 1 | 2 | 4-16 | 4-32 |
Line fault monitor for open circuit | Yes | |||
Line fault monitor for short circuit | Yes | |||
Line fault monitor for detector removal | Yes, if End of Line Monitor Unit fitted in place of End of Line Resistor | |||
End of Line device | 6.8k Ω,5% tolerance, 0.25W (colour code-blue,grey,red,gold) | |||
Detector continuity diodes | Silicon 1N4001 or Schottky type (required if End of Line Monitor Unit fitted to give Detector Removal Fault) | |||
Call point resistor value | 470 to 680 Ω, 0.225 or 0.5 watt | |||
Maximum number of smoke/heat detectors per zone | 20 (based on a total detector current of 2mA, each detector consuming 100μA).Note: if End of Line Monitor Unit is fitted, for correct operation maxmum voltage drop must not exceed 12 volts. | |||
Maximum number of manual call points per zone | No limit | |||
Sounder circuit specification |
|
|||
Number of general circuits | 2 | |||
End of line resistor value | 6.8k Ω,5% tolerance, 0.25W (colour code-blue,grey,red,gold) | |||
Line fault monitor for open circuit | Yes | |||
Line fault monitor for short circuit | Yes | |||
Outputs fused AT | 400mA | |||
Maximum number of bells @ 20mA of each sounder output | 20 | |||
Fuses |
|
|||
Battery fuse | 1.5A F 20mm | |||
Sounder outputs | 500mA F 20mm | |||
Fire and fault output |
|
|||
Output type | NC and NO relay | |||
Maximum current | 100mA | |||
Connection block |
|
|||
Largest acceptable conductor size | 2.5mm2 | |||
Smallest acceptable conductor size | 0.75mm2 | |||
Size and weight |
|
|
||
Dimensions(mm) | 272*200*70mm | 320*231*90mm | 395X502X124 | 362X565X124 |
Weight (without batteries) | 4kg | 5kg | 7kg | 8kg |
Weight (with batteries) | 5.8kg | 6.8kg | 9.6kg | 12.5kg |