Categories
Price: | US $ 10/Piece |
---|---|
Trade Terms: | FOB,CFR,CIF |
Min Order: | 10/Piece |
Pay Type: | L/C,T/T,Western Union |
Markets: | North America,South America,Eastern Europe,Southeast Asia,Africa,Oceania,Mid East,Eastern Asia,Western Europe |
---|---|
Breaking Capacity: | Low Voltage Circuit Breakers |
Operation: | Manual Type |
Speed: | Normal Type Circuit Breaker |
Arc-extinguishing Medium: | Air |
Installation: | Fixed |
Structure: | MCCB |
Poles Number: | 3 |
Certification: | CCC |
Specification | ||||
Type | DZ108-1 | DZ108-3 | DZ108-4 | |
Poles | 3 | 3 | 3 | |
Rated current (A) | 20 | 32 | 63 | |
Rated voltage (V) | 660 | 660 | 660 | |
Rated insulation voltage (V) | 660 | 750 | 750 | |
Current setting voltage (V) | 0.1~0.16 0.16~0.2 5 0.25~0.4 0.4~0.63 0.63~1 1~1.6 1.6~2.5 2~3.2 2.5~4 3.2~5 4~6.3 5~8 6.3~10 8~12.5 10~16 14~20 | 1~1.6 1.6~2.5 2.5~4 4~6.3 6.3~10 8~12.5 10~16 12.5~20 16~25 22~32 | 6.3~10 10~16 16~25 22~32 28~40 36~50 45~63 45~56 | |
Power of controlled motor (KW) | 220V | 5.5 | 9 | 18 |
380V | 10 | 16 | 32 | |
660V | 13 | 26 | 58 | |
Mechanical life(1×104) | 10 | 10 | 3 | |
Protective feature | 1.05le | Not act within 2hrs | ||
1.2le | Act within 2hrs | |||
12le | Action snap |