Product Specifications
| Prod Model: |
DZ15 |
| Markets: |
South America,Southeast Asia,Africa,Oceania,Mid East,Eastern Asia,Western Europe |
| Color: |
White and Black |
| Type: |
Circuit Breaker |
| Function: |
Overload, Shortcircuit Protection |
| Arc-extinguishing Medium: |
Air |
| Structure: |
MCCB |
| Breaking Capacity: |
Low Voltage Circuit Breakers |
| Certification: |
CCC |
| Operation: |
Electric Type |
| Installation: |
Insert |
| Speed: |
Normal Type Circuit Breaker |
| Poles Number: |
2p,3p |
Product Description
MCCB DZ15
Scope of application:
DZ15 series molded case circuit breaker (hereinafter referred to as breaker) is applied in the circuit with AC 50Hz, rated voltage up to 380V and rated current up to 100A. As the purpose of distributing power energy. It also can be used to protect the circuit and motor from overload and short-circuit as infrequent transformation of the circuit and the starting of motor.
This product complies with GB140048.2, GB14048.4, IEC60947-2 and IEC60947-4 standards.
Normal working conditions and installation condition:
1. Maximum ambient air temperature does not exceed 40 ° C, and the minimum is not less than -5 ° C. The average temperature does not exceed 35 ° C within 24h;
2. The altitude of installation site does not exceed 2000m;
3. Relative humidity of the surrounding air temperature is less than 50% at 40 ° C. At a lower temperature, it can be a higher relative humidity. For example at 20 ° C, it is up to 90%. When it occurs the occasional condensation due to temperature changes, appropriate measures should be taken.
4. Pollution degree: Class 3;
5. Installation category: Main circuit of circuit breaker is ClassIII. Control and auxiliary circuits are ClassII.
Structure and working principle:
This series circuit breaker consists of contacts, operation mechanism, hydraulic electromagnetic release, arc extinguishing mechanism and plastic shell. When the protected circuit or motor occur overload and short circuit, the circuit breaker can be reliably broken. Multi-poles breaker can be Agency linkage. As long as a pole occur overload action, it will make all poles simultaneously break.
Main technical parameter is shown in Table 1.
Protection characteristic of overcurrent release used in power distribution protection is shown in Table 2.
Protection characteristic of overcurrent release used in motor protection shown in Table 3.
We also produce many various of circuit breakers.
Welcome to contact with us if you are interested in. We are looking forward to starting the cooperation with you
Contact:
Tel: +86-577-57189983
Mobile Phone: +86-13616776676
Fax: +86-577-62713637
|
Model No. |
Max. rated current of shell degree(A) |
Rated current ln(A) |
Pole No. |
Rated voltage Un(V) |
lcu kA |
Arcing distance mm |
|
DZ15-40 |
400 |
6,10,16,20,25,32,40 |
1 |
220 |
3 |
≤ 50 |
|
2 |
|
3 |
380 |
|
DZ15-100 |
100 |
50,63,80,100 |
3 |
380 |
5 |
≤ 70 |
|
Ambient air temperature |
Distribution circuit breaker |
|
Current setting multiple |
Convention time |
Starting state |
|
ln ≤ 63A |
Ln>63A |
|
+30 degree Celsius±2 degree Celsius |
1.05ln |
Not trip within 1h |
Not trip within 2h |
Cold state starts |
|
1.30ln |
Trip within 1h |
Trip within 2h |
Thermal state starts |
|
3.00ln |
Return time≥2s |
Return time≥2s |
Cold state starts |
|
At any appropriate temperature |
10.00ln |
<0.2s Trip |
<0.2s Trip |
Cold state starts |
|
+20 degree Celsius±2 degree Celsius |
1.05ln |
Not trip within 1h |
Not trip within 2h |
Cold state starts |
|
|
1.30ln |
Trip within 1h |
Trip within 2h |
Thermal state starts |
|
Ambient temperature |
Motor protection circuit breaker |
|
Current setting multiple |
Current setting multiple |
Starting state |
|
+20 degree Celsius±2 degree Celsius |
1.05ln |
Not trip within 2h |
Cold state starts |
|
1.20ln |
Trip within 2h |
Thermal state starts |
|
1.50ln |
<2min Trip |
Thermal state starts |
|
6.0ln |
Return time>1s |
Cold state starts |
|
At any appropriate temperature |
12.00ln |
<0.2s Trip |
Cold state starts |
|
-5 degree Celsius±2 degree Celsius |
1.05ln |
Not trip within 2h |
Cold state starts |
|
1.30ln |
Trip within 2h |
Thermal state starts |
|
+40 degree Celsius±2 degree Celsius |
1.00ln |
Not trip within 2h |
Cold state starts |
|
1.20ln |
Trip within 2h |
Thermal state starts |
The company is a professional manufacturer of low-voltage electrical components, power automation equipment, electrical construction oriented electrical manufacturing companies, but it is also a collection of scientific research, commerce and trade as one integrated enterprise. The national water system network, identified as "networks" of recommended by the State Economic and Trade Commission.
Over the years the company, through constant practice, innovation, effort, enterprise achieved rapid development. The company's existing high-, MID-level engineers and technicians 31 people, 816 employees, supporting assist 126 enterprises; same time, the company has established a marketing network outside by point to the surface, China to over 300 domestic sales outlets now. The products are widely used in power plants, banks, hospitals, hotels, chemical, military, factories and other infrastructure, buildings and residential areas.
Company's major series specifications of the products have passed the national CCC certification, while continuing to deepen the quality of management, and actively with the international standards, the full implementation of ISO9001 international quality system certification, and passed the quality system certification, some products made UL, EC body CE certificate, the product is well received by domestic and foreign users.
To face the challenges of the new century, the company will continue to carry forward the "advocate science, sticking to integrity and pragmatic, harmonious development" spirit of enterprise, is committed to the construction of "science and technology enterprises" TELI Foundation became a powerful cultural cohesion and brand influence modern enterprise.