I.Scope of Application
DZ47 high breaking MCB is mainly applied to the line of AC frequency 50/60Hz, rated operated voltage 230/400V or below, with rated current up to 63A. It is used to provide overload or short-circuit protection for electrical circuits or equipment of modern buildings. It can also used as infrequent operation or isolation.
Structural features of DZ47 high breaking MCB is assembled by plastic housing, operating mechanism, contact arc extinguishing system and tripping mechanism, etc. The housing is made of special plastic with characteristics of flame retardant, high impact and light weight. So is the operating mechanism, which can ensure its delicacy & reliability and get minimum rotary inertia at the meanwhile. Thus, the tripping mechanism will operate quickly once the short circuit occurs. The tripping mechanism is made up of bimetallic strip overload inverse time-lag tripping mechanism and short-circuit momentary electromagnetic mechanism. Its contact system adopts special arc guiding angle and extinguish chamber, which have a notable current limiting effect.
It is widely applied in office buildings, residential buildings and other similar buildings to provide both overload and short circuit protection for its lighting, distribution line and equipment. It can also be used for infrequent line switching under normal circumstances. This product complies to Standard of IE60898 & GB10963.1. Our DZ47 high breaking MCB has also been CCC and CE approved.
II. Types and Specifications
DZ-MPCB, /Design Code/ Function Code/ Frame Size /Usage Code/Number of Poles
III. Normal Operating Conditions
Ambient air temperature: -5ºC~+40ºC. Please contact our technical department if the temperature for your usage is out of range.
Altitude: ≤2000
Atmosphere Condition: when ambient air temperature is up to 40ºC, the relative air humidity can not exceed 50%. While at a lower temperature, a higher relative humidity can be allowed. For example, the RH could reach to 90% when the temperature is 25 degrees Celsius.
Due to the temperature variation, slight condensation may occur occasionally. Please pay your attention to take appropriate measures.(Like a scupper hole).
Vertically mounted. Tilt angle ≤5%
Ensure that there is no distinct shake or shock at the installation site.
The circuit breaker should be used by reducing capacity, if it is installed within a protective enclosure and there is also several circuit breakers mounted against each other, the derating factor should range from 0.7 to 0.8, which may depend on the enclosure material. For metal, choose higher value. For plastic , the lower value is better.
IV. Main Parameters and Technical Performance
Main Specification:
Rated Current: 6A,10A,16A,20A,25A,32A,40A,50A,63A
Number of Poles: 1P; 2P; 3P; 4P.
Instantaneous tripping type: a. C type(5ln~10ln); b. D type(10ln~16ln).
Life: a: Electrical Life (times): ≥ 3000
B: Mechanical Life (times): ≥8000
Frame size lnm(A) | Rated current ln(A) | Number of poles(P) | Rated voltage Ue(V) | Breaking capacity lcn(A) |
63 | 6,10,16,20,25,32,40 | 1,2 | 230 | 4500~6000 |
2,3,4 | 400 | |||
50,63 | 1,2 | 230 | 3000~4500 | |
2,3,4 | 400 |
Test | Type | Test current | Initial state | Time limit | Expected result |
a | B,C,D | 1.13ln | Cold state | t≤1h | Non-tripping |
b | B,C,D | 1.45ln | Follow to item a | t<1h | Tripping |
c | B,C,D | 2.55ln | Cold state | 1s1s32A) | Tripping |
d | B | 3ln | Cold state | t≤0.1s | Non-tripping |
C | 5ln | ||||
D | 10ln | ||||
e | B | 5ln | Cold state | t<0.1s | Tripping |
C | 10ln | ||||
D | 16ln |
V. Outline and Installation Dimension
VI. Notes
Level A Quality: red copper accessory, flame-retardant housing, silver point
Level B Quality: brass copper accessory, general plastic housing, alloy point
Level C Quality: iron accessory, general plastic, copper point
Please kindly keep us informed if you need Level A quality. Also, the quality of product can be customized if your order quantity can meet our demands. Since Level C quality is not good enough, please also note us if there is any needs. Our quotation of DZ47 MCB is based on Level B quality, normally without tax. The price will be increased by 10% if VAT invoice is needed.
P.s.: Our company are looking forward to cooperating with large-scale or large-demand companies, to take over outsourcing processing & manufacturing. We specialize in the product for 12 years, with the quality and safety be ensured.
VII. Order Notice
The following information shall be provided in ordering:
Product Name and Type: DZ47-63 MCB/ DZ47 high breaking MCB.
Instantaneous Tripping Rated Current: Like, 30A.
Number of Poles: Like, 4P.
Order Quantity: Like ,230pcs.
Usage code: type B for microcomputer, C for power distribution, D for motor protection.
Ordering Example: DZ47-63 MCB, 3P, 32A, 1500pcs, type C.