Surge Arrester Distribution 11kv
Product Specifications
| Prod Model: |
YH10W-33 |
| Markets: |
North America,South America,Eastern Europe,Southeast Asia,Africa,Oceania,Mid East,Eastern Asia,Western Europe |
| Moa: |
Under 10PC |
| Structure: |
Zinc Oxide Arrester |
| Type: |
Distribution |
| Brand: |
Oeipower Jingguan |
| Certification: |
Xihari |
| Shape: |
Round |
| Installation: |
Pole Line |
Product Description

Metal oxide surge arrester (MOA) is recognized as the upto-date overvoltage protector which ,due to the inherent superior nonlinear V-A characteristics and steep-wave response of metal oxide varistors ,can suppress overvoltages to a relative low level ,thus providing a reliable protection for insulation of electrical apparatus.
The basic technical parameters are complied with the technical specification of IEEE and IEC60099-4
arrester are heavy duty distribution class surge arrester. These are gapless design
incorporating highly non-linear metal oxide varistor, with a discharge rated current of 10 kA. The housing can be polimeric arresters are tested in accordance with the lastest standard ANSI/IEEE C62.11 for metal oxide
arresters, and also with IEC 60099-4.
They consistently withstand the following
minimum type test:
* High Current-Short duration: 2
current surges of 100 kA-crest magnitude
20 shoots of 100 kA amplitude.
* Low Current-Long duration: 20
shoots (or impulses) of 250 A amplitude
and 2.000 μs duration.
* Duty Cycle: 20 discharges with a
current surge of 10 kA magnitude and
8/20 μs wave shape followed by 2 discharges
with a current surge of 100 kA
magnitude.
| Item | Description | Units | 33kV |
|
|
| Required | Guaranteed Value |
| 1 | Type |
| Metal Oxide, Gapless | Metal Oxide, Gapless |
| 2 | Material |
| Polymeric | Polymeric |
| 3 | Nominal System Volt rating | kV | 33 | 33 |
| 4 | Maximum System rating | kV | 36 | 36 |
| 5 | Power Frequency | Hz | 50 | 50 |
| 6 | Peak Voltage rating: Ur | kV | 30 | 30 |
| 7 | Maximum Voltage rating: Uc | kV | 21kV | 21kV |
| 6 | One minute power frequency withstand voltage | kV | 70 | 70 |
| 7 | Basic Insulation level | kVp | 170 | 170 |
| 8 | Specific creepage distance | mm/kV | 25 | 25 |
| 9 | Nominal Discharge Current with 8/20 microsecond wave | kA | 10 | 10 |
| 10 | Fittings and Accessories -Fasteners for stacking units along with clamp & terminal connectors. |
| Yes | Yes |


Voltage Rating (Ur) (kVrms) | MCOV (UC)1 (kVrms) | Max. Equiv. FOW2 (kV Crest) | Max. Switch Surge3 (kV Crest) | Max .Discharge voltage (kV Crest) Using 8/20 μs Current Impulse |
1.5 kA | 2.5 kA | 3.0 kA | 5.0 kA | 10 kA | 20 kA | 40 kA |
| 3 | 2.55 | 10.0 | 7.9 | 8.5 | 8.8 | 8.9 | 9.4 | 10.2 | 11.3 | 13.3 |
| 6 | 5.10 | 19.9 | 15.8 | 16.9 | 17.5 | 17.7 | 18.8 | 20.4 | 22.5 | 26.6 |
| 9 | 7.65 | 29.9 | 23.7 | 25.4 | 26.2 | 26.6 | 28.2 | 30.5 | 33.8 | 39.9 |
| 10 | 8.40 | 32.9 | 26.3 | 28.1 | 29.2 | 29.6 | 31.3 | 33.9 | 37.4 | 43.9 |
| 12 | 10.20 | 39.8 | 31.6 | 33.8 | 34.9 | 35.4 | 37.6 | 40.7 | 45.0 | 53.1 |
| 15 | 12.70 | 49.8 | 39.5 | 42.2 | 43.6 | 44.3 | 47.0 | 50.9 | 56.3 | 66.4 |
| 18 | 15.30 | 59.7 | 47.4 | 50.7 | 52.3 | 53.1 | 56.4 | 61.0 | 67.5 | 79.7 |
| 21 | 17.00 | 69.7 | 55.3 | 59.1 | 61.0 | 62.0 | 65.7 | 71.2 | 78.7 | 92.9 |
| 24 | 19.50 | 79.6 | 63.2 | 67.6 | 69.7 | 70.8 | 75.1 | 81.3 | 90.0 | 106.2 |
| 27 | 22.00 | 89.6 | 71.1 | 76.0 | 78.4 | 79.7 | 84.5 | 91.5 | 101.2 | 119.5 |
| 30 | 24.40 | 99.5 | 78.8 | 84.2 | 87.4 | 88.7 | 93.9 | 101.7 | 112.0 | 131.7 |
| 33 | 26.80 | 109.5 | 86.7 | 92.6 | 96.2 | 97.6 | 103.3 | 111.9 | 123.2 | 114.9 |
| 36 | 30.00 | 119.4 | 94.6 | 101.0 | 104.9 | 106.4 | 112.7 | 122.0 | 134.4 | 158.0 |
Voltage Rating (Ur) (kVrms) | MCOV (UC)1 (kVrms) | Max. Equiv. FOW4 (kV Crest) | Max. Switch Surge3 (kV Crest) | Max .Discharge voltage (kV Crest) Using 8/20μs Current Impulse |
1.5 kA | 2.5 kA | 3.0 kA | 5.0 kA | 10 kA | 20 kA | 40 kA |
| 3 | 2.55 | 10.4 | 7.8 | 8.5 | 8.8 | 8.9 | 9.3 | 9.9 | 10.9 | 12.4 |
| 6 | 5.10 | 20.7 | 15.5 | 16.9 | 17.5 | 17.7 | 18.6 | 19.8 | 21.8 | 24.7 |
| 9 | 7.65 | 31.0 | 23.3 | 25.4 | 26.2 | 26.6 | 27.9 | 29.7 | 32.7 | 37.0 |
| 10 | 8.40 | 34.5 | 25.9 | 28.2 | 29.1 | 29.5 | 31.0 | 33.0 | 36.3 | 41.1 |
| 12 | 10.20 | 41.3 | 31.0 | 33.8 | 34.9 | 35.4 | 37.2 | 39.6 | 43.5 | 49.3 |
| 15 | 12.70 | 51.7 | 38.8 | 42.2 | 43.6 | 44.2 | 46.5 | 49.5 | 54.4 | 61.6 |
| 18 | 15.30 | 62.0 | 46.5 | 50.7 | 52.3 | 53.1 | 55.8 | 59.4 | 65.3 | 73.9 |
| 21 | 17.00 | 72.3 | 54.3 | 59.1 | 61.0 | 61.9 | 65.14 | 69.3 | 76.2 | 86.2 |
| 24 | 19.50 | 82.6 | 62.1 | 67.6 | 69.7 | 70.9 | 74.4 | 79.2 | 87.0 | 98.5 |
| 27 | 22.00 | 92.9 | 69.8 | 76.0 | 78.4 | 79.6 | 83.7 | 89.1 | 97.9 | 110.8 |
| 30 | 24.40 | 103.3 | 77.6 | 84.4 | 87.1 | 88.4 | 93.0 | 99.0 | 108.8 | 123.1 |
| 33 | 26.80 | 113.7 | 85.4 | 92.8 | 95.8 | 97.3 | 102.3 | 108.9 | 119.7 | 135.4 |
| 36 | 30.00 | 123.9 | 93.1 | 101.3 | 104.5 | 106.0 | 111.6 | 118.8 | 130.6 | 147.7 |
1. GENERAL Metal oxide surge arrester (MOA) is recognized as the upto-date overvoltage protector which ,due to the inherent superior nonlinear V-A characteristics and steep-wave response of metal oxide varistors ,can suppress overvoltages to a relative low level ,thus providing a reliable protection for insulation of electrical apparatus. The basic technical parameters are complied with the technical specification of Chinese Standard GB11032-2000 which is exactly equivalent to IEC60099-42. THCHNICAL DATAZINC OXIDE PROTECTIVE CHARACTERISTICS (5kA NORMAL DUTY POLYMER)Voltage Rating (Ur) (kVrms) | MCOV (UC)1 (kVrms) | Max. Equiv. FOW2 (kV Crest) | Max. Switch Surge3 (kV Crest) | Max .Discharge voltage (kV Crest) Using 8/20 μs Current Impulse |
1.5 kA | 2.5 kA | 3.0 kA | 5.0 kA | 10 kA | 20 kA | 40 kA |
| 3 | 2.55 | 10.0 | 7.9 | 8.5 | 8.8 | 8.9 | 9.4 | 10.2 | 11.3 | 13.3 |
| 6 | 5.10 | 19.9 | 15.8 | 16.9 | 17.5 | 17.7 | 18.8 | 20.4 | 22.5 | 26.6 |
| 9 | 7.65 | 29.9 | 23.7 | 25.4 | 26.2 | 26.6 | 28.2 | 30.5 | 33.8 | 39.9 |
| 10 | 8.40 | 32.9 | 26.3 | 28.1 | 29.2 | 29.6 | 31.3 | 33.9 | 37.4 | 43.9 |
| 12 | 10.20 | 39.8 | 31.6 | 33.8 | 34.9 | 35.4 | 37.6 | 40.7 | 45.0 | 53.1 |
| 15 | 12.70 | 49.8 | 39.5 | 42.2 | 43.6 | 44.3 | 47.0 | 50.9 | 56.3 | 66.4 |
| 18 | 15.30 | 59.7 | 47.4 | 50.7 | 52.3 | 53.1 | 56.4 | 61.0 | 67.5 | 79.7 |
| 21 | 17.00 | 69.7 | 55.3 | 59.1 | 61.0 | 62.0 | 65.7 | 71.2 | 78.7 | 92.9 |
| 24 | 19.50 | 79.6 | 63.2 | 67.6 | 69.7 | 70.8 | 75.1 | 81.3 | 90.0 | 106.2 |
| 27 | 22.00 | 89.6 | 71.1 | 76.0 | 78.4 | 79.7 | 84.5 | 91.5 | 101.2 | 119.5 |
| 30 | 24.40 | 99.5 | 78.8 | 84.2 | 87.4 | 88.7 | 93.9 | 101.7 | 112.0 | 131.7 |
| 33 | 26.80 | 109.5 | 86.7 | 92.6 | 96.2 | 97.6 | 103.3 | 111.9 | 123.2 | 114.9 |
| 36 | 30.00 | 119.4 | 94.6 | 101.0 | 104.9 | 106.4 | 112.7 | 122.0 | 134.4 | 158.0 |
High-Current Short Duration: 2 current surges of 65kA magnitude and 4/10μs wave shape.Low-Current Long Duration : 20 current surges of 75 A magnitude and 2000μs duration .1 MCOV=Maximum Continuous Operating Voltage that may be applied continuously between the terminals of the arrester.2 The equivalent Front-of -Wave is the maximum discharge voltage for a 5kA impulse current wave which produces a voltage wave cresting in 0.35μs. 3 Based on a switching surge current impulse of 45×90μs, 500 amperes.4 The equivalent Front-of-Wave is the maximum discharge voltage for a 10kA impulse current wave which produces a voltage wave cresting in 0.5μs.ZINC OXIDE PROTECTIVE CHARACTERISTICS (10kA NORMAL DUTY POLYMER) Voltage Rating (Ur) (kVrms) | MCOV (UC)1 (kVrms) | Max. Equiv. FOW4 (kV Crest) | Max. Switch Surge3 (kV Crest) | Max .Discharge voltage (kV Crest) Using 8/20μs Current Impulse |
1.5 kA | 2.5 kA | 3.0 kA | 5.0 kA | 10 kA | 20 kA | 40 kA |
| 3 | 2.55 | 10.4 | 7.8 | 8.5 | 8.8 | 8.9 | 9.3 | 9.9 | 10.9 | 12.4 |
| 6 | 5.10 | 20.7 | 15.5 | 16.9 | 17.5 | 17.7 | 18.6 | 19.8 | 21.8 | 24.7 |
| 9 | 7.65 | 31.0 | 23.3 | 25.4 | 26.2 | 26.6 | 27.9 | 29.7 | 32.7 | 37.0 |
| 10 | 8.40 | 34.5 | 25.9 | 28.2 | 29.1 | 29.5 | 31.0 | 33.0 | 36.3 | 41.1 |
| 12 | 10.20 | 41.3 | 31.0 | 33.8 | 34.9 | 35.4 | 37.2 | 39.6 | 43.5 | 49.3 |
| 15 | 12.70 | 51.7 | 38.8 | 42.2 | 43.6 | 44.2 | 46.5 | 49.5 | 54.4 | 61.6 |
| 18 | 15.30 | 62.0 | 46.5 | 50.7 | 52.3 | 53.1 | 55.8 | 59.4 | 65.3 | 73.9 |
| 21 | 17.00 | 72.3 | 54.3 | 59.1 | 61.0 | 61.9 | 65.14 | 69.3 | 76.2 | 86.2 |
| 24 | 19.50 | 82.6 | 62.1 | 67.6 | 69.7 | 70.9 | 74.4 | 79.2 | 87.0 | 98.5 |
| 27 | 22.00 | 92.9 | 69.8 | 76.0 | 78.4 | 79.6 | 83.7 | 89.1 | 97.9 | 110.8 |
| 30 | 24.40 | 103.3 | 77.6 | 84.4 | 87.1 | 88.4 | 93.0 | 99.0 | 108.8 | 123.1 |
| 33 | 26.80 | 113.7 | 85.4 | 92.8 | 95.8 | 97.3 | 102.3 | 108.9 | 119.7 | 135.4 |
| 36 | 30.00 | 123.9 | 93.1 | 101.3 | 104.5 | 106.0 | 111.6 | 118.8 | 130.6 | 147.7 |
High-Current Short Duration: 2 current surges of 65kA magnitude and 4/10μs wave shape.Low-Current Long Duration : 20 current surges of 75 A magnitude and 2000μs duration .1 MCOV=Maximum Continuous Operating Voltage that may be applied continuously between the terminals of the arrester.2 The equivalent Front-of -Wave is the maximum discharge voltage for a 5kA impulse current wave which produces a voltage wave cresting in 0.5μs. 3 Based on a switching surge current impulse of 45×90μs, 500 amperes.4 The equivalent Front-of-Wave is the maximum discharge voltage for a 10kA impulse current wave which produces a voltage wave cresting in 0.5μs. 3.APPLICATION CONDITION3.1 Normal Service condition Surge arresters which conform to this standard shall be suitable for normal operation under the following normal service conditions: Ambient air temperature within the range of -40ºC to +40ºC. Solar radiation : The effects of maximum solar radiation (1.1kW/m2)have been taken into account by preheating the test specimen in the type tests. If there are other heat sources near the arrester, the application of the arrester shall be subject to an agreement between the manufacturer and the purchaser. Altitude is not exceeding 1000m. Frequency of the A.C power supply is not less than 48Hz but not more than 62HZ. Power frequency voltage applied continuously between the terminals of the arrester is not exceeding its continuous operating voltage. Mechanical conditions ;no strong vibration. Pollution conditions: no requirement at this time. 3.2 Abnormal Service ConditionsSurge arresters subject to other than normal application or service conditions may require special consideration in design, manufacture or application. The use of this standard in case of abnormal service conditions is subject to agreement between the manufacturer and the purchaser. 4 OVERALLDIMENSIONS 5kA NORMAL DUTY POLYMERRated Voltage | 3 | 6 | 9 | 10 | 12 | 15 | 18 | 21 | 24 | 27 | 30 | 33 | 36 |
| A | 98mm |
| B | 68mm |
| C | 200 | 246 | 246 | 246 | 246 | 302 | 350 | 350 | 350 | 420 | 420 | 480 | 480 |
| D | 138mm |
Creepage Distance | 180 | 390 | 390 | 390 | 365 | 500 | 660 | 660 | 700 | 890 | 890 | 970 | 1100 |
10kA NORMAL DUTY POLYMERRated Voltage | 3 | 6 | 9 | 10 | 12 | 15 | 18 | 21 | 24 | 27 | 30 | 33 | 36 |
| A | 106mm |
| B | 78mm |
| C | 200 | 246 | 246 | 246 | 246 | 302 | 350 | 350 | 350 | 420 | 420 | 480 | 480 |
| D | 138mm |
Creepage Distance | 180 | 390 | 390 | 390 | 365 | 500 | 660 | 660 | 700 | 890 | 890 | 970 | 1100 |
5. INSTALLATION AND PRECAUTION5.1 The surge arrester is fixed to the supporting structure by fitting-bracket, and connecting its top terminal to H V wire of electrical apparatus ,which is protected ,with 8-16 mm2 copper wire, connecting its chassis cover to the terminal of operation counter, connecting the other terminal of operation counter to the ground wire, or connecting its chassis cover to the ground directly. 5.2 The surge arrester should be lain close to the electrical apparatus, which is protected ,for protective effects. When the transformer is protected ,the distance between the arrester and on the low voltage side of a distribution transformer in case any damage to the insulation caused by forward-backward over voltage 5.3 After bring the surge arrester into operating ,should be do preventive test every two years, measuring the leakage current of arrester at DA 1mA.5.4 Please don't break open the surge arresters.5.5 This product is warranted against defects in workmanship and materials .If any failure ,resulting from a defect in either workmanship or material, is occurred under the normal using within one years form the date of purchase ,we shall replace it in free of charge.
Our company is one of factory Of OEIpower, Local in No. 15, Tongbai, Industrial Zone, Nanyang City, Hean Province, China, OEIpower have been created in 2007 to provide complete solutions for the Energy sector, mainly power generation, transmission and distribution markets. OEIpower is able to lead turn-key projects and also cooperate in specific parts of engineering projects. Regarding products, OEIpower is creating a solid sales and distribution network in order to manage the main components involved in the energy sector and markets.
It is a professional Manufacturing. Meanwhile, it is specialized in power transmission and distribution products such as Insulators, Drop-out Fuse, Fuse link, Load Interrupter Air Switchs, Surge arrester, Outdoor Off-Load Isolator Switch Disconnector switch etc. We have won many orders for World markets, Like South Korea, Spain, Malaysia, Thailand, Yemen, etc.
Our most of the products have passed the type test performed by Electric Power lin Aeeseeory Quality Inspection Center of electric Power industry, such as Xi'an High Voltage Research Insitute. And IST off-load switch type IST-12KV/400A already passed CENTRAL POWER RESEARCH INSTITUTE HIGH-VOLTAGE LABORATORY India. Our 12KV 8KA Drop Out fuse already passed the ASTA testing in the year 2015.
Promise of After-sales Service
To ensure the quality of After-sales Service, We have established the After-sales Service Department, and compiled the process of after-sales service, We require service-man should passion, cordial, patient, careful, considerate and instant for customers. Our general service: After receive telephone, the local service-man direct to the site to solve the problem, to security reasonable interest of the customer. When finishing all the work. Service men must fill the bill of customers' feedback suggestion, and ask the customers' signature. Then deliver it to the After-sales Service Department as feedback information, then to the designing and exploiting department. Special condition: Directly send someone from company to dealing, Our products' guarantee days are two years. Within those days, Quality problems of causing by customers. We'll repair freely, Causing by customers using, operating and keeping un-properly, we'll repair permanently and charge properly. Out of guarantee days, we'll repair with charge (fee of component and repairing).
Main Technical Testing Equipment
No.
Name of checkout equipment
1
86-G Type impulse peak Voltage test equipment
2
MY-4KV Type voltage dependent resistor test equipment
3
MDA-30 Type DC parameter test equipment
4
Metal-oxide surge arrester bleeder current test equipment
5
500KV power frequency withstand voltage test equipment
6
HR-3 Type loop resistance test equipment
7
GKC-6 Type High-voltage switch mechanical properties test equipment
8
5A heavy current test equipment
9
YHN-8 Type auto power frequency withstand voltage console
10
CJV-800 Type impulse with stand voltage test equipment
11
CJI-1 Type impulse with stand current test equipment
12
JF-1 Type complementary Metal-oxide surge arrester instrument for measuring partial discharge
13
XR-2 Type power frequency test equipment
14
MD-1A Type Metal-oxide surge arrester electrification test equipment
15
JZ-800 Type AC/DC high voltage test equipment
16