Kingsine Electric Automation Co., Ltd. >> Protection Relay Test Set (K3063I)

Protection Relay Test Set (K3063I)

Protection Relay Test Set (K3063I)
Price: Negotiable/Piece
Trade Terms: FOB
Min Order: 1/Set
Pay Type: L/C,T/T
Friendly PC software for easy operation!

K30 series relay tester is extremely design for overseas user, with Friendly PC software as your need, unique features and functions helps you all the way!

1. Unique self-protection system assure the powerful protection when instrument is operating, automatic stop the output when the network is abnormal;
2. Unique power switch and amplifier technology, so the output precision and power efficiency and factor are increased, which conforms to international tendency of energy save and environmental protection;
3. With alarm function of housing grounding testing and external voltage input, to guaranty personal security;
4. Two in one of meter and source, with function of both internal and external testing, self-calibration, oscillograph, and the duration of each oscillograph reaches 50S (optional function);
5. Offer independent Aux. DC to tested devices, 0 ~ 300V/0.6A (Poleless and adjustable);
6. Function of transducer and energy meter testing (optional function);
7. Testing interface offer unique output monitoring function and Pre-curve-tracing function, helps more on the spot analysis
Voltage  generators
Setting 
Range
7-phase  AC  (L-N) 7  x  0  ...  300  V 
2-phase  AC  (L-L) 2  x  0  ...  600  V
Power 7-phase  AC  (L-N) 7  x  110VA,     at  0  ...  300  V
2-phase  AC  (L-L) 2  x  220VA,     at  0  ...  600  V
Accuracy < 0.07%  reading  +  0.03%  range  guaranteed 
at  0  ...  300  V
< 0.02%  reading  +  0.01%  range  typical 
at  0-300V
Resolution 1mV
Current  generators
Setting 
Range
6-phase  AC  (L-N) 6  x  0  ...  30  A
3-phase  AC  (2L-N) 3  x  0  ...  60  A  (Group  A  II  B)
1-phase  AC  (3L-N) 1  x  0  ...  180  A 
Power 6-phase  AC  (L-N) 6x  450VA  ,   at  0  ...  30A 
3-phase  AC  (2L-N) 3x  520VA,     at  0  ...  60A  (Group  A  II  B) 
1-phase  AC  (3L-N) 1  x  1000  VA,     at  0  ...  180A  (Max. )
Accuracy < 0.07%  reading  +  0.06%  range  guaranteed  at  0-30A 
< 0.02%  reading  +  0.02%  range  typical  at  0-30A
Resolution 1mA
Generators,     general
Frequency Range 0  ...  1000  Hz
Accuracy  /  drift Error  <   0.001Hz  at  10  ...  65Hz,  
Error  <   0.01Hz    at  65Hz...450Hz
Error  <   0.02Hz    at  450Hz...1000Hz
Resolution 0.001Hz
Phase Range -  360°   ...  +360°
Accuracy  /  drift Error  <   0.2  °
Resolution 0.1°
Timer Range Infinite
Accuracy  /  drift Error< 0.1ms
DC  generators
Voltage  ranges 0  ...  300V/180W
Current  ranges 0  ...  20A/300W
Accuracy < 0.07%  reading  +  0.03%  range  guaranteed  at  0-300V 
< 0.04%  reading  +  0.02%  range  typical  at  0-300V
< 0.14%  reading  +  0.06%  range  guaranteed  at  0-20A
< 0.05%  reading  +  0.02%  range  typical  at  0-20A
Resolution 1mA;   1  mV
Aux  DC  Supply
Range 0...300V/150W
Binary  inputs
Number 8  pairs
Compatible  Voltage 10V  ...  250V    DC
Binary  outputs
Number 4  Pairs
Capacity 250V/3A        AC/DC
Synchronization
Synchronization  mode GPS
Harmonic
Harmonic  overlap  times 2  ...  20  times
Power  supply
Nominal  input  voltage 220VAC± 20%
Power 1000VA
Nominal  frequency 47Hz… . 65Hz
Environmental  conditions
Operation  temperature -5° C  ...  55  ° C
Storage  temperature -20° C  ...  75  ° C
Humidity  range 5%  ...  90  %,     non-condensing
Weight 20  KG
Dimensions 460(D)× 140  (W)× 360  (H)  mm
PC  connection RJ45,  
Protection  Relay  Test  Set: 
Model Channels AC  Outputs
K3063i  /  K3063Li 10  output  channels 6*30A/3*40A/4*300V
K3030i  /  K3030Li 7  output  channels 3*30A/4*300V
K3066 13  output  channels 6*20A/3*40A/7*130V
K3063 10  output  channels 6*20A/3*40A/4*130V
K3040 7  output  channels 3*40A/4*130V
K3030 7  output  channels 3*30A/4*130V
Major  functions:
Items IEEE(R)  No.
Synchronization  relay  
Fault  transplay  
GPS  Synchronization   
Overcurrent  relays 50/76
Inverse  time  overcurrent  relays 51
Undercurrent  relays 37
Ground  fault  relays 50
Directional  overcurrent  relays 67
Directional  ground  fault  relays 67N
Overvoltage  relays 59
Undervoltage  relays 27
Directional  voltage  relays 91
Directional  power  relays 32
Power  factor  relays 55
Differential  protection  (differential  circuits) 87
Distance  protection  equipment  (phase  by  phase) 21
Negative  sequence  overcurrent  relays 46N
Motor  overload  protection 51/86
Automatic  reclosing  devices  79
Tripping  relays 94
Voltage  regulating  relays  
Overimpedance  relays,     Z>  
Underimpedance  relays,     Z  
Time-delay  relays  
Prod Model: K3063I
Markets: North America,South America,Eastern Europe,Southeast Asia,Africa,Oceania,Mid East,Eastern Asia,Western Europe
1. Chinese top manufacturer mainly on: Protection Relay Test Set; Standard Power & Calibrator; Portable Reference Standard
RTU-Tester. PMC Series. Cable Fault Tester.
2. Hi-tech enterprise with CE Certificate and ISO9001: 2000 Certificate.
3. All-in-One design with integrate PC and amplifier Comprehensive product line-from single-phase, 3-phase to 6-phase.
4. 3-year free quality warranty and life maintenance.
5. Wide references & honored users in many kinds of Electricity power generation, Transmission, Distribution.
6. Suitable working for many world famous relay protection devices: Such as AREVA, ABB, ALSTOM, SCHNEIDER, GE, SEL etc.

Send your message to this manufacturer

  • Kingsine Electric Automation Co., Ltd.

More >

Other Products From This Manufacturer