Technical Specification | |||||||
Performance Indexes | CPU306 | ||||||
K306-24DT | K306-24AT | K306-24DR | K306-24AR | ||||
CPU | 16-bit industrial | ||||||
Execution Speed | Typical Bool instruction time: <0.5 μ S Word operation time: <48 μ S Arithmetic operation time for integers: <65 μ S Arithmetic operation time for floating points: <150 μ S | ||||||
DI Points | 14XDC24V | ||||||
DO Points | 10XDC24V | 10Xrelay | |||||
User Program Memory | FRAM, 8KB/about 1,200 steps | ||||||
Program Backup | Permanent storage, without the need of battery | ||||||
Memory Area | Variable storage area (V area): 4KB System storage area (SM area): 300 bytes Internal storage area (M area): 32 bytes | ||||||
Data Retention Characteristic | Configure with the programming software: V area, C (counter) area | ||||||
Retention Mode and Period | Adopt super capacitors and support a retention period of not less than 144 hours upon power failure under normal temperature. | ||||||
Data Backup Characteristic | Perform backup operations VB3648~VB3902 according to user instructions, 255 bytes in total | ||||||
Backup Mode and Time | FRAM, 255 bytes in total (writing operation for 10 billion times), permanent backup | ||||||
Floating Points | Supported; the whole V area can be used for floating points | ||||||
Programming Language Supported | Ladder Drawing (LD), Instruction List (IL) | ||||||
Instruction Set | Basic instructions: 55; expansion instructions: 252 | ||||||
Password Protection | Yes | ||||||
Max. I/O | Digital data: 88 in total (64 DI and 64 DO respectively); Analog data: 16 in total (16 AI and 16 AO respectively) | ||||||
Counter | 128 | ||||||
Operation Mode of Counter | Addition, subtraction | ||||||
Counter Range | -32768~32767 | ||||||
Counting Value Retention Function | Yes | ||||||
Timer | 128 1 ms time base: 4 10 ms time base: 16 100 ms time base: 108 | ||||||
High-speed Counter | 6 high-speed counters where, single-phase counters: 6, with a maximum frequency of 30 KHz where, dual-phase counters: 4, with a maximum frequency of 20 KHz | ||||||
Pulse Output | 2, PTO (Pulse Train Output)/PWM (Pulse Width Modulation output); Maximum output frequency: 20 KHz | ||||||
Analog Potentiometer | 2, 10-bit resolution, values corresponding to internal registers | ||||||
Interruption Function | Timing interruption: 2, 1ms resolution; Timer interruption: T2/T3, 1ms resolution; Edge interruption: 4, rising edge or falling edge optional; High-speed interruption, communication interruption | ||||||
Real-time Clock | Yes, with an error not greater than 2 minutes/month under a temperature of 25 ° C The user can use the software to set/read: year, month, day, hour, minute, second, week. Standby batteries are used to supply power for the real-time clock upon power failure. Under normal temperature, the accumulative retention period of the real-time clock upon power failure is up to 50,000 hours. | ||||||
Number of Connectable Expansion Modules | 4; regardless of types | ||||||
COM Port | 1, RS232 or RS485; Supported working modes: Programming, Modbus-RTU (slave), Free protocol | ||||||
Equipment Connected with COM Port | RS232/RS485: PC (for programming), third-party HMI panel, third-party serial communication equipment (for example, instruments, bar code reader, etc.) | ||||||
Input Power Supply | DC24V±20% | AC85~265V | DC24V+/-20% | AC85~265V | |||
Sensor Load Power Supply | DC24V, max. 500 mA | ||||||
Dimensions (L*W*H) | 125X114X70mm |