Product Specifications
| Markets: |
North America,South America,Eastern Europe,Southeast Asia,Africa,Oceania,Mid East,Eastern Asia,Western Europe |
| Size: |
Miniature |
| Theory: |
Electromagnetic Relay |
| Usage: |
Household Appliances Relay, Communication Relay |
| Protective Characteristics: |
Open Relay |
| Load: |
Medium Power Relay |
| Action Principle: |
Electromagnetic Type |
Product Description
1.Application
CJX2N series AC contactor is suitable for frequency 50/60Hz,rated insulation voltage up to1000V,rated operation current 9~150A under AC-3 duty.It is mainly used for making/breakingelectric circuits at a long distance & for frequent starting/stopping & controlling AC Motors.It isused in combination with thermal relay to compose a magnetic motor starter. The products com-ply with IEC60947-4-1 standard.
2.Specification
| Type | CJX2N-09 | CJX2N-12 | CJX2N-18 | CJX2N-25 | CJX2N-32 | CJX2N-38 | CJX2N-40 |
Rated working current Ie (A) AC-3 Ue≤440V | 9 | 12 | 18 | 25 | 32 | 38 | 40 |
| Rated hear current Ith (A) | 25 | 25 | 32 | 40 | 50 | 50 | 60 |
| Rated insulation voltage Ui (V) | 690 | 690 | 690 | 690 | 690 | 690 | 1000 |
| Rated operating voltage Ue (V) Max | 690 | 690 | 690 | 690 | 690 | 690 | 1000 |
| Rated operational power in AC-3 Pe (KW) | 220/230V | 2.2 | 3 | 4 | 5.5 | 7.5 | 9 | 11 |
| 380/400V | 4 | 5.5 | 7.5 | 11 | 15 | 18.5 | 18.5 |
| 415/440V | 4 | 5.5 | 9 | 11 | 15 | 18.5 | 22 |
| 500V | 5.5 | 7.5 | 10 | 15 | 18.5 | 18.5 | 22 |
| 660/690V | 5.5 | 7.5 | 10 | 15 | 18.5 | 18.5 | 30 |
| Rated operational power inAC-4 Pe (KW) | 220/230V | 1.5 | 1.5 | 2.2 | 3 | 4 | 4 | 4 |
| 380/400V | 2.2 | 3.7 | 4 | 5.5 | 7.5 | 7.5 | 9 |
| 415/440V | 2.2 | 3 | 3.7 | 5.5 | 7.5 | 7.5 | 9/11 |
| 500V | 3 | 4 | 5.5 | 7.5 | 9 | 9 | 11 |
| 660/690V | 4 | 5.5 | 7.5 | 10 | 11 | 11 | 15 |
| Frequency of operation (I/h) | | 1200 | 1200 | 1200 | 1200 | 1000 | 1000 | 1000 |
| Electrical endurance (x104) | AC-3 | 100 | 100 | 100 | 100 | 80 | 80 | 80 |
| AC-4 | 20 | 20 | 20 | 20 | 20 | 20 | 15 |
| Mechanical endurance (x106) | | 15 | 15 | 15 | 15 | 15 | 15 | 6 |
| Operating voltage range of coil | Close voltage:(0.85~1.1)Us Open voltage:(20%~75%)Us |
| Power consumption of coil (VA) | Atracting | 7 | 7 | 7 | 7 | 7 | 7 | 20 |
| Starting | 70 | 70 | 70 | 70 | 70 | 70 | 200 |
| Rated insulation voltage ofauxitiary contacts (V) | 690 | 690 | 690 | 690 | 690 | 690 | 690 | 690 |
| Conventional thermal current ofauxitiary contacts (A) | 10 | 10 | 10 | 10 | 10 | 10 | 10 | 10 |
| Auxitiary contacts speecification | AC-15:360VA DC-13:33W |
| Type | CJX2N-50 | CJX2N-65 | CJX2N-80 | CJX2N-95 | CJX2N-115 | CJX2N-150 |
Rated working current Ie (A) AC-3 Ue≤440V | 50 | 65 | 80 | 95 | 115 | 150 |
| Rated hear current Ith (A) | 80 | 80 | 125 | 125 | 200 | 200 |
| Rated insulation voltage Ui (V) | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 |
| Rated operating voltage Ue (V) Max | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 |
| Rated operational power in AC-3 Pe (KW) | 220/230V | 15 | 18.5 | 22 | 25 | 30 | 40 |
| 380/400V | 22 | 30 | 37 | 45 | 55 | 75 |
| 415/440V | 25/30 | 37 | 45 | 45 | 59 | 80 |
| 500V | 30 | 37 | 55 | 55 | 75 | 90 |
| 660/690V | 33 | 37 | 45 | 45 | 80 | 100 |
| Rated operational power inAC-4 Pe (KW) | 220/230V | 5.5 | 7.5 | 7.5 | 9 | 9 | 11 |
| 380/400V | 11 | 11 | 15 | 15 | 18.5 | 22 |
| 415/440V | 11 | 11/15 | 15 | 15 | 18.5 | 22 |
| 500V | 15 | 18.5 | 22 | 22 | 30 | 37 |
| 660/690V | 18.5 | 22 | 25 | 25 | 30 | 45 |
| Frequency of operation (I/h) | | 1000 | 1000 | 750 | 750 | 750 | 750 |
| Electrical endurance (x104) | AC-3 | 60 | 60 | 60 | 60 | 60 | 60 |
| AC-4 | 15 | 15 | 15 | 15 | 15 | 15 |
| Mechanical endurance (x106) | | 6 | 6 | 4 | 4 | 4 | 4 |
| Operating voltage range of coil | Close voltage:(0.85~1.1)Us Open voltage:(20%~75%)Us |
| Power consumption of coil (VA) | Atracting | 20 | 20 | 20 | 20 | 22 | 22 |
| Starting | 200 | 200 | 200 | 200 | 300 | 300 |
| Rated insulation voltage ofauxitiary contacts (V) | 690 | 690 | 690 | 690 | 690 | 690 | 690 |
| Conventional thermal current ofauxitiary contacts (A) | 10 | 10 | 10 | 10 | 10 | 10 | 10 |
| Auxitiary contacts speecification | AC-15:360VA DC-13:33W |
3. Standard Control Circuit Voltage
| Volts | 24 | 42 | 48 | 110 | 220 | 230 | 240 | 380 | 400 | 415 | 440 | 500 | 660 |
| 50Hz | B5 | D5 | E5 | F5 | E5 | F5 | U5 | Q5 | V5 | N5 | R5 | S5 | Y5 |
| 60Hz | B6 | D6 | E6 | F6 | E6 | F6 | U6 | Q6 | - | - | R6 | | |
| 50/60Hz | B7 | D7 | E7 | F7 | E7 | F7 | U7 | Q7 | V7 | N7 | R7 | | |
4. Characteristic
Contactor and other auxiliary blocks.
| Contactor | | Auxiliary Blocks | | Relative Products |
| | + | | = | |
| | + | | = | |
| | + | | = | |
5. Outline and Mounting Dimension
| | 09 | 12 | 18 | 25 | 32 | 38 | 40 | 50 | 65 | 80 | 95 | 115 | 150 |
| b | 76.6 | 76.6 | 76.6 | 76.6 | 76.6 | 76.6 | 127 | 127 | 127 | 127 | 127 | 158 | 158 |
| c | 87 | 87 | 87 | 94 | 94 | 94 | 116 | 116 | 116 | 123.8 | 123.8 | 132 | 132 |
![]()
Elecal Industrial Automation is Specializing in the manufacture and export of low-voltage and hight-voltage electrical products in China. Such as MCB, MCCB, ELCB, RCD, Contactor, Fuse, Relay, Switch, Distribution Box etc.
All the manufacturing process of the products is in strictly conformity to international IEC standard and we have established and perfected quality control procedures in accordance with ISO9001 international quality management system.